Application
These cables are used for connection of signal and
control devices in industry, steam and hydro electric
power stations, traffic, etc. May be laid into cable
channels, indoor and ground applying additional protection.
Construction
• Plain copper conductor, as per VDE 0295 cl.1 solid
type (HD 383)
• PVC core insulation, YI4 as per VDE 0207/4 (DIV 4
DIN VDE 0276-603)
• Colour coded to VDE 0276-603 (HD 186).
• Cores are number coded and one of them is green/yellow
ground core.
• Cores are strained in concentric layers
• Inner covering PVC or ruber mass
• Overall PVC outer jacket type YM3 as per VDE 0207/5,
(DMV 5, DIN VDE 0276-603) black coloured.
• PVC self-extinguishing, test method B according to
DIN VDE 0472/804.
Technical data
• Temperature range
- flexing -5°C to + 50°C
- stationary -30°C to + 70°C
• Working voltage Uî/U 0,6/1KV
• Test voltage 4KV
• Specific insulation resistance at 70°C min. 1010
Ω x cm
• Bending radius min:
- for single core cá. 15 x Ø
kabel
- for multi core cá. 12 x Ø
kabel
• Permissible tensile stress with cable grip Cu- conductor,
max 50 N/mm2
|