english makedonski deutsch ruskii
  contact
 
profile
products
Flexible Conductors
Instalation Conductors
Telephone, data and control cables
Power cables 1 KV
Middle voltage cables
Connecting cables
Overseas cables according UL and CSA standards
contact info
 

ISO certificate
  Power cables 1 KV  
NYY NYY-signal NAYY NYBY NAYBY NYCWY NYCY X00/0-A N2XY NA2XY E-XAY2Y
General info   Tehnical construction  
E-XAY2Y - General info

Application

Cables are applied for power distribution in city networks, industrial plants and on the places where mechanical damages are expected. May be laid in the ground, cable ducts and in open air.

Construction

• Plain aluminium conductor, as per ÖVE-K23a/1980, cl.1 or cl.2, solid or stranded type, (HD 383)

• PVC core insulation typ DIV 4,VDE 276-603;HD 603.1(YI4 as per DIN VDE 0207/4)

• Colour coded to ÖVE-K23/1974 (DIN VDE 0276-603)

• Additional signal-command copper core, with cross section 2,5mm2, red coloured (black coloured 1,5mm2 on request)

• Cores are strained concentrically

• Inner covering, EPDM rubber mass

• HDPE outer jacket, black, type DMP2 according DIN VDE 0276-603 (HD603.1), the hardness > 60°Sh


Technical data

• Temperature range
- flexing -5°C to + 50°C
- stationary -20°C to + 70°C

• Working voltage Uo/U 0,6/1KV

• Test voltage 4KV

• Specific insulation resistance at 70°C min. 1010 Ω x cm

• Bending radius min:
- for single core cá. 15 x Ø kabel
- for multi core cá. 12 x Ø kabel

• Permissible tensile stress with cable grip, max 30 N/mm2



profile products contact info