Application
Power cables for energy supply are installed in open
air, in underground, in water, indoors, in cable ducts,
power stations, for industry - and distribution boards
as well as in subscriber networks, where mechanical
damages are not to be expected.
Construction
• Plain aluminium conductor, as per VDE 0293 cl.1 or
cl.2 solid or stranded type (HD 383)
• PVC core insulation, YI4 as per DIN VDE 0207 part
4 (DIN VDE 0276 - 603, type DIV4)
• Colour coded to DIN VDE 0276-603.
• Additional signal-command core with cross section
1.5mm2, black coloured(red
coloured 2.5mm2 on
request)
• Cores twisted concentrically
• Inner covering PVC or rubber mass
• PVC outer jacket, black, YM3 as per VDE 0207 part
5 (type DMV 5 to DIN VDE 0276-603)
• PVC self-extinguishing, test met-hod B according
to DIN VDE 0472 part 804 (HD 405.1)
Technical data
• Temperature range
- flexing -5°C to + 50°C
- stationary -30°C to + 70°C
• Working voltage Uo/U 0,6/1KV
• Test voltage 4KV
• Specific insulation resistance at 70°C min. 1010
Ω x cm
• Bending radius min:
- for single core cá. 15 x
Ø kabel
- for multi core cá. 12 x
Ø kabel
• Permissible tensile stress with cable grip for Al-
conductor max. 30 N/mm2
|