Application
Cables are applied for power distribution in city networks,
industrial plants and on the places where mechanical
damages are expected. May be laid in the ground, cable
ducts and in open air.
Construction
• Plain aluminium conductor, as per DIN VDE 0295 cl.1or
cl.2 solid or stranded type,
• PVC core insulation, YI4 as per DIN VDE 0207/4
• Colour coded to DIN VDE 0293
• Additional signal-command core with cross section
1.5mm2,black coloured(red
coloured 2.5mm2 on
request)
• Cores are strained concentrically,
• Inner covering PVC or rubber mass,
• Armouring of two steel tapes,
• PVC outer jacket, black, YM3 as per DIN VDE 0207
part 5,
• PVC self-extinguishing, test method B acc. to DIN
VDE 0472 part 804 and IEC 332-1,
Technical data
• Temperature range
- flexing -5°C to + 50°C
- stationary -30°C to + 70°C
• Working voltage Uo/U 0,6/1KV
• Test voltage 4KV
• Specific insulation resistance at 70°C min. 1010
Ω x cm
• Bending radius min:
- for single core cá. 15 x Ø
kabel
- for multi core cá. 12 x Ø
kabel
• Permissible tensile stress with cable grip for Cu-
conductor max 30 N/mm2
|