Application
Power cables for energy supply are installed in open
air, in underground, in water, concrete, indoors, in
cable ducts, power stations, for industry and distribution
boards as well as in subscriber networks, where mechanical
damages are not to be expected.
Construction
• Plain copper conductor, as per HD 383( cl.1 or cl.2
stranded type VDE 0295).
• XLPE core insulation, type DIX3 as per DIN VDE 0276
603,HD 603.1 (2XI1 as per DIN VDE 0207 part 22)
• Colour coded to DIN VDE 0276-603. In respect to 3
+ 1/2conductors,
whereby only one conductor is allowed to contain a smaller
cross section and permitted to place as insulated core
green
• yellow as 1/2conductor,
stranded in layer.
• Cores twisted concentrically
• Inner covering EPDM- rubber mass
• PVC outer jacket, black, type DMV 6 to DIN VDE 0276-603,HD
603.1(YM3 as per VDE 0207 part 5)
• PVC-mass is self-extinguishing, test method according
to HD 405.1 ( DIN VDE 0472 part 804-B)
Technical data
• Temperature range
- flexing -5°C to + 50°C
- stationary -30°C to + 90°C
• Working voltage Uo/U 0,6/1KV
• Test voltage 4KV
• Specific insulation resistance at 90°C min. 1014
Ω x cm
• Bending radius min:
- for single core ca. 15 x Ø
kabel
- for multi core ca. 12 x Ø
kabel
• Permissible tensile stress with cable grip, max 50
N/mm2
|