Application
For middle voltage power distribution in distribution
networks (6/10(12);12/20(24); 20/35(42)) kV, generating
plants, sub-stations and industrial plants. May be laid
into the ground and moisture areas, cable channels and
premises.
Construction
• Strand of soft annealed copper or aluminium DIN VDE
0295 cl.2 (HD383).
• Semi conducting layer around conductor
• XLPE isolation, DIX8 as per DIN VDE 0276-620 part
1.
• Semi conducting layer around isolation
• Semi-conductive swell able tape helicoidally wrapped
• Electric protection: copper wires and tape cross
section 16 or 25 mm2
• Non- conductive swell able tape helicoidally wrapped
around the screen
• PE outer sheath (black), type DMP2 as per DIN VDE
0276-620 part 1.
• Sheat can be made from PVC mass type DMV6, red (or
black) coloured and then is marked like N2XS(F)2Y or
NA2XS(F)2Y
Technical data
• Operating temperature at:
- nominal load 90°C
- emergency load, max. 130°C
- short circuit max. 250°C
• Dielectric factor of losses, 50 Hz, 20°C (0.8-3)x10-4
• Partial discharge 2pC
• Test voltage (5 min) 2.5UoKV
• Spec.volume insulation resistance, 20°C, min 1015
Ω x cm
• Intensity of electric field max. 6.9-5.3kV/mm
• Permitted bending radius min 15 x Ø
kabel
• Permitted temperature during laying, min -5°C
• Tensile force during the laying must not exceed:
- for cables with Cu conductors 50N/mm2
- for cables with Al conductors 30N/mm2
• Test of water penetration 125x4h, 90°C
|