Application
For middle voltage power distribution in distribution
networks(6/10(12);12/20(24); 20/35(42)) kV , generating
plants, sub-stations and industrial plants. May be laid
into the ground, in open air, cable channels and premises.
Construction
• Strand of soft annealed copper or aluminium DIN VDE
0295 cl.2, (HD383)
• Semi conducting layer around conductor
• XLPE isolation, type DIX8 as per DIN VDE 0276-620
part 1.
• Semi conducting layer around isolation
• Semi-conductive tape helicoidally wrapped
• Electric protection: copper wires and tape cross
section 16 or 25 mm?
• Screened cores are laid-up
• Inner covering applied around the laid-up cores
• PVC outer sheath (red), type DMV6 as per DIN VDE
0276-620 part 1.*
Technical data
• Operating temperature at:
- nominal load 90°C
- emergency load max. 130°C
- short circuit max. 250°C
• Dielectric factor of losses, 50 Hz, 20°C (0.8-3)x10-4
• Partial discharge 2pC
• Test voltage (5 min) 2.5UoKV
• Spec. volume insulation resistance, 20°C, min
1015 Ω x cm
• Intensity of electric field max. 6.9-5.3kV/mm
• Permitted bending radius min 15 x Ø
kabel
• Permitted temperature during laying, min -5°C
• Tensile force during the laying must not exceed:
- for cables with Cu conductors 50N/mm2
- for cables with Al conductors 30N/mm2
|