Application
For middle voltage power distribution in distribution
networks (6/10(12);12/20(24)) kV. May be put on on the
overhead lines in old and residential areas. Provides
a shortcut to electrification without affecting the
townscape and its environs. This cables can be strung
safely on the same poles with low-voltage and telecommunication
cables.
Construction
• Round, stranded and compacted aluminium conductors
cl.2, according to MKS N.C0.015
• Semi conducting layer around conductor
• XLPE isolation, XI 1 as per MKS N.C0.195
• Semi conducting layer around isolation
• Semi-conductive swell able tape helicoidally wrapped
• Electric protection: copper wires and tape cross
section 16 mm2 or 2,5mm2
• Non-conductive swell able tape helicoidally wrapped
around the screen
• PE outer sheath for each phase conductor and steel
messenger (black), type EP1 as per MKS N.C0.195
• Galvanized steel messenger 50 mm2
as per MKS N.C1.702. Mass of zink coated as per MKS.C.B6.051
• Three single-phase cables twisted around a steel
messenger as an aerial bundled cable
Technical data
• Operating temperature at:
- nominal load 90°C
- emergency load max. 130°C
- short circuit max. 250°C
• Dielectric factor of losses, 50 Hz, 20°C (0.8-3)x10-4
• Partial discharge 2pC
• Test voltage (5 min) 2.5UoKV
• Spec. volume insulation resistance, 20°C, min
1015 Ω x cm
• Intensity of electric field max. 6.9-5.3kV/mm
• Test of water penetration 125x4h, 90°C
• Permitted bending radius min 10 x Ø
kabel
• Permitted temperature during laying, min -5°C
• Breaking load of messenger, min 60kN
• Modulus of elasticity of messenger : 175kN/mm2 |